FieldServer Honeywell Zellweger IR 148 User Manual

A Sierra Monitor Company  
Driver Manual  
(Supplement to the FieldServer Instruction Manual)  
FS-8700-102 Honeywell Zellweger IR-148  
Manual  
APPLICABILITY & EFFECTIVITY  
Effective for all systems manufactured after May 1, 2001  
Driver Version:  
1.01  
Document Revision: 9  
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual  
Page 3 of 19  
1.  
Honeywell Zellweger IR-148 Description  
The Honeywell Infrared Gas Monitor (Model IR-148) detects solvents and gases such as  
HCFCs, HFCs and PFCs. IR-148 can have 1, 4 or 8 sampling points. This InfraTox driver  
reports gas values, alarms and troubles from IR-148 having either 1 or 8 sampling points.  
The serial driver can emulate a client or a server. The FieldServer and IR-148 device are  
connected using a RS-485 network.  
As a Client: The driver listens passively for messages from the Honeywell Zellweger IR-148  
t
and stores data extracted from the messages. The driver cannot poll the IR-148 device for  
data. The driver records some additional data age information (which is stored in the  
FieldServer’s Data Arrays) because messages do not always contain information about all  
sensors and depending on the IR-148 operational mode (e.g. Locked mode.), may never  
contain information other than for one sensor.  
As a Server: The Server side of this driver has been developed primarily to test the Client side  
driver as part of FieldServer’s QA program. The driver sends messages reporting the state of  
the samples. The Server driver can also be locked to report the status/value of one particular  
sample channel.  
It is possible to connect two Honeywell Zellweger units (IR-148) on one RS-485 network  
provided that one unit is configured as a single point unit (IR-148 1 point) and the other as an 8  
point unit (IR-148 8 point). At this stage only one device with 8 points has been tested.  
To allow for the possibility that the device is connected on a RS-485 network with other devices  
(such as the relay module option) messages that are not 49 bytes long and which do not begin  
with 0xB1 will be ignored. The Driver will, however, provide statistics for the ignored as well as  
the processed messages.  
To see supported messages and the way the Driver stores Data, refer to Appendix A.2  
Max Nodes Supported  
FieldServer Mode  
Client  
Server  
Nodes  
2
2
Comments  
Tested only 1 node (IR-148 8 Point) per port  
Developed to test Client side of the Driver.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual  
Page 4 of 19  
2.  
Driver Scope of Supply  
2.1. Supplied by FieldServer Technologies for this driver  
FieldServer Technologies  
PART #  
Description  
FS-8917-16  
FS-8700-102  
RJ45 to terminal connector cable.  
Driver Manual.  
2.2.  
Provided by the Supplier of 3rd Party Equipment  
Required 3rd Party Hardware  
2.2.1.  
Part #  
Description  
NONE  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual  
Page 5 of 19  
3.  
Hardware Connections  
The FieldServer is connected to the Honeywell Zellweger IR-148 Device as shown in  
connection drawing.  
Configure the device according to manufacturer’s instructions  
OR  
FS-X40  
INFRATOX UNIT  
+
-
G
OTHER DEVICES  
Serial  
ORANGE/WHITE  
BROWN  
FS-X20  
INFRATOX UNIT  
FS-8917-16  
+
-
G
BLUE/WHITE  
(408)-262-2299  
Honeywell Zellweger  
IR-148 Device FieldServer  
Connection Diagram  
BASE NAME:  
FILE NAME: VisioDocument  
DATE: 03/07/07  
BY: MC  
*Other devices must not transmit Honeywell Zellweger IR-148 49 byte messages  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual  
Page 6 of 19  
4.  
Configuring the FieldServer as a Honeywell Zellweger IR-148 Client  
For a detailed discussion on FieldServer configuration, please refer to the FieldServer  
Configuration Manual. The information that follows describes how to expand upon the factory  
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files  
provided with the FieldServer).  
This section documents and describes the parameters necessary for configuring the FieldServer  
to communicate with a Honeywell Zellweger IR-148 Server having one or eight sensors.  
4.1.  
The configuration file tells the FieldServer about its interfaces, and the routing of data  
required. In order to enable the FieldServer for Honeywell Zellweger IR-148  
Data Arrays/Descriptors  
communications, the driver independent FieldServer buffers need to be declared in the  
“Data Arrays” section, the destination device addresses need to be declared in the “Client  
Side Nodes” section, and the data required from the Servers needs to be mapped in the  
“Client Side Map Descriptors” section. Details on how to do this can be found below.  
Note that in the tables, * indicates an optional parameter, with the bold legal value being the  
default.  
Section Title  
Data_Arrays  
Column Title  
Function  
Legal Values  
Up to 15 alphanumeric  
characters  
Data_Array_Name  
Provide name for Data Array  
Float, Bit, UInt16, SInt16,  
Provide data format. Each Data Packed_Bit,  
Byte,  
Data_Array_Format  
Array can only take on one format.  
Packed_Byte,  
Swapped_Byte  
Number of Data Objects. Must be  
larger than the data storage area  
required by the Map Descriptors for  
the data being placed in this array.  
Data_Array_Length  
1-10,000  
Example  
// Data Arrays  
Data_Arrays  
Data_Array_Name,  
DA_R1,  
DA_R2,  
DA_CTL_R1,  
DA_CTL_R2,  
Data_Format,  
Float,  
Float,  
Uint16,  
Uint16,  
Data_Array_Length  
100  
100  
1
1
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual  
Page 7 of 19  
4.2.  
Client Side Connection Descriptors  
Section Title  
Connections  
Column Title  
Function  
Legal Values  
Specify which port the device is P1-P8 (with 232/485 converter), R1-  
Port  
connected to the FieldServer  
Specify protocol used  
Specify baud rate  
Specify parity  
Specify data bits  
R21  
Protocol  
Baud*  
Parity*  
Data_Bits*  
Stop_Bits*  
Handshaking*  
InfraTox or Infra-Tox  
19200 (Vendor limitation)  
None (Vendor limitation)  
8 (Vendor limitation)  
1
Specify stop bits  
Specify hardware handshaking  
None (Vendor limitation)  
Example  
// Client Side Connections  
Connections  
Port,  
R1,  
Protocol,  
InfraTox,  
Baud,  
19200, None,  
Parity,  
Stop_Bits  
1
4.3.  
Section Title  
Nodes  
Client Side Node Descriptors  
Column Title  
Function  
Legal Values  
Node_Name  
Provide name for node  
Up to 32 alphanumeric characters  
Irrelevant for this driver as long  
as only one Node is connected.  
Otherwise the Node-ID should be  
the number of points/sensors for  
Node_ID  
which the Zellweger unit is 0-255  
configured. A unique Node_ID is  
recommended for each Zellweger  
Unit as it may be useful in  
exposing Node status information  
Protocol  
Port  
Specify protocol used  
InfraTox, Infra-Tox.  
Specify at which port the device is  
connected to the FieldServer  
Ports P1-P8 can be with 232/485  
converter.  
P1-P8 (with 232/485 converter),  
R1-R21  
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction  
manual for details of the ports available on specific hardware.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual  
Page 8 of 19  
Example  
// Client Side Nodes  
Nodes  
Node_Name,  
DEV1,  
Node_ID,  
1,  
Protocol,  
InfraTox,  
Port  
R1  
4.4.  
4.4.1.  
Client Side Map Descriptors  
FieldServer Related Map Descriptor Parameters  
Column Title Function Legal Values  
Name of this Map Up to 32 alphanumeric  
Map_Descriptor_Name  
Data_Array_Name  
Descriptor  
Name of Data Array  
where data is to be  
stored  
FieldServer  
characters  
One of the Data Array  
names from “Data Array”  
section above  
in  
the  
Starting location in Data 0 to maximum specified in  
Data_Array_Offset  
Function  
Array  
“Data Array” section above  
Function of Client Map  
Descriptor.  
Passive_Client  
4.4.2.  
Driver Related Map Descriptor Parameters  
Column Title  
Function  
Legal Values  
One of the node names  
specified in “Client Node  
Descriptor” above  
Name of Node to fetch  
data from  
Node_Name  
0-Maximum of Data Array  
length.  
Length  
Length of Map Descriptor  
Expand Storage per point  
Refer to 0.  
‘YES’ every thing else  
considered as ‘NO’  
Extended_Storage*  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual  
Page 10 of 19  
5.  
Configuring the FieldServer as a Honeywell Zellweger IR-148 Server  
For a detailed discussion on FieldServer configuration, please refer to the FieldServer  
Configuration Manual. The information that follows describes how to expand upon the factory  
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files  
provided with the FieldServer).  
This section documents and describes the parameters necessary for configuring the FieldServer  
to report sensor data to Honeywell Zellweger IR-148 Client. As a Server this driver sends Gas  
value, Alarm, Trouble and Lock point messages. The driver can be locked to send data for only  
one particular sensor.  
The configuration file tells the FieldServer about its interfaces, and the routing of data required.  
In order to enable the FieldServer for Honeywell Zellweger IR-148 communications, the driver  
independent FieldServer buffers need to be declared in the “Data Arrays” section, the  
FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, and the  
data to be provided to the Clients needs to be mapped in the “Server Side Map Descriptors”  
section. Details on how to do this can be found below.  
Note that in the tables, * indicates an optional parameter, with the bold legal value being the  
default.  
5.1.  
Server Side Connection Descriptors  
Section Title  
Connections  
Column Title  
Function  
Legal Values  
Specify which port the device is P1-P8  
connected to the FieldServer  
Specify protocol used  
(with  
232/485  
Port  
converter), R1-R22  
InfraTox or Infra-Tox  
Protocol  
110 – 115200, standard  
baud rates only  
9600  
Even, Odd, None, Mark,  
Space  
Baud*  
Specify baud rate  
Specify parity  
Parity*  
Data_Bits*  
Specify data bits  
7, 8  
Stop_Bits*  
Specify stop bits  
1
Handshaking*  
Specify hardware handshaking  
RTS, RTS/CTS, None  
Example  
// Server Side Connections  
Connections  
Port,  
R1,  
Protocol,  
InfraTox,  
Baud,  
19200,  
Parity,  
None,  
Data_Bits  
8
2
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction  
manual for details of the ports available on specific hardware.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual  
Page 11 of 19  
5.2.  
Server Side Node Descriptors  
Section Title  
Nodes  
Column Title  
Node_Name  
Function  
Legal Values  
Up to 32 alphanumeric  
characters  
Provide name for node  
Commonly used parameter but  
irrelevant for this driver as  
Protocol is node-less.  
A unique Node_ID is, however,  
Node_ID  
recommended  
for  
each 1-255  
Honeywell Zellweger IR-148  
Unit as it may be useful in  
exposing  
Node  
status  
information  
Protocol  
Port  
Specify protocol used  
Specify at which port the device  
is connected to the FieldServer P1-P8  
Ports P1-P8 can be used with converter), R1-R2  
232/485 converter.  
InfraTox, Infra-Tox.  
(with  
232/485  
Example  
// Server Side Nodes  
Nodes  
Node_Name,  
DEVR1,  
Node_ID,  
1,  
Protocol,  
InfraTox,  
Port  
R1  
5.3.  
5.3.1.  
Server Side Map Descriptors  
FieldServer Specific Map Descriptor Parameters  
Column Title Function Legal Values  
of this  
Name  
Descriptor  
Map Up to 32 alphanumeric  
characters  
Map_Descriptor_Name  
Name of Data Array where One of the Data Array  
data is to be stored in the names from “Data Array”  
Data_Array_Name  
FieldServer  
section above  
Starting location in Data 0 to maximum specified in  
Data_Array_Offset  
Function  
Array  
“Data Array” section above  
Wrbc  
Function of Server Map  
Descriptor  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual  
Page 12 of 19  
5.3.2.  
Driver Specific Map Descriptor Parameters  
Column Title  
Function  
Legal Values  
One of the node names  
specified in “Server Node  
Descriptor” - section 5.2  
1-Maximum of Data Array  
length.  
Name of Node to which data  
has to be sent.  
Node_Name  
Length  
Length of Map Descriptor  
Name of Data Array used to  
lock the sensor. Driver will  
report data for the locked  
sensor only.  
One of the Data Array  
names from “Data Array”  
section above  
Da_Byte_Array_Name*  
Specifies  
Da_Byte_Array_Name  
Data array. This memory  
offset  
for  
location will be checked every  
time if the user has locked a  
sensor.  
1-Maximum of Data Array  
length.  
Data_Byte_Offset*  
If this parameter is not  
specified, the driver will use the  
Data_Array_Offset value.  
For quality assurance this  
parameter is used to send a  
message to a Client from a  
Map_Descriptor_Name*.ini file.  
With the use of this function  
Data_Array_Offset value will be  
used as line number from INI to  
send.  
INFRA_SIMULATION:  
only  
numbered line will be sent to  
Client by the Map Descriptor.  
INFRA_SIMULATION_ALL:  
Starting at the numbered line all  
lines will be sent one by one to  
the Client until the end of the  
file is reached.  
INFRA_SIMULATION  
INFRA_SIMULATION_ALL  
INFRA_SIM_ALL_REPEAT  
Infra_Func  
INFRA_SIM_ALL_REPEAT:  
Repeatedly  
Starting  
from  
numbered line to end of the file  
all lines will be sent to Client  
one by one by this single Map  
Descriptor.  
Note: Ini must show all bytes as  
two  
character  
hex  
representation and first line of  
should be  
// FILE_IN_HEX_FORMAT  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual  
Page 15 of 19  
Appendix A. Advanced Topics  
Appendix A.1. Supported Functions at a glance  
Message Types  
Gas Value Message  
Trouble Message  
Notes  
Message reports a gas value and units.  
Message reports a trouble for one sensor  
Message used to flash Honeywell Zellweger  
IR-148 display  
Message reports an alarm (C/W/A) for one  
sensor  
Blank Message  
Alarm Message  
Locked Point Message  
Unit is locked onto a single sample.  
Other 49 byte messages beginning 0xb1  
Other 49 byte messages  
Other messages  
Discarded but driver report stats on these  
messages see 0.  
Appendix A.2. How Data is stored by the Driver.  
The Driver can be configured to store data in one of two ways:  
a) Default: One Set of consecutive Data Array elements is used for each Honeywell  
Zellweger IR-148-8.8-Channel Unit. One set per point/sensor.  
Offset Sensor Contents  
Description  
Alarm  
Trouble  
or Set non-zero if alarm or a trouble has been reported. Set to  
0
1
zero if neither are currently being reported.  
0 = None  
1 = Caution  
2 = Warning  
1
1
Alarm Type  
3 = Alarm  
0 = None  
1 = Trouble  
2
3
1
1
Trouble  
Gas value multiplied by 100 is stored here. When stored, if  
configured, scaling will be applied.  
Gas Value  
4
5
6
1
1
1
Gas Units  
Gas Units  
Gas Units  
1st 3 bytes of gas units are written here as ASCII characters.  
0 = Enabled  
1 = Disabled  
7
8
9
1
1
1
State  
Gas  
Valid  
Gas  
Age  
Value 1 = Gas Value updated with most recent message.  
0 = Gas Value not updated.  
Value In seconds since last update.  
Initial (and max) value = 0xffff  
Time since last message containing data about this sensor.  
In seconds since last update.  
Initial (and max) value = 0xffff  
Sensor Data  
Age  
10  
1
11..21  
22..32  
33..43  
44..54  
55..65  
66..76  
77..87  
2
3
4
5
6
7
8
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual  
Page 16 of 19  
b) Extended storage : If the FieldServer is configured to use extended storage then data  
will be stored as below  
Offset  
Sensor Contents  
Description  
Non-zero if alarm or a trouble has been reported.  
Zero if neither are currently being reported.  
0 = None, 1 = Caution, 2 = Warning, 3 = Alarm  
0=None, 1=Trouble  
0
1
Alarm or Trouble  
1
2
1
1
Alarm Type  
Trouble  
Gas value multiplied by 100 is stored here. When  
stored, if configured, scaling will be applied.  
3
1
Gas Value  
4
5
6
7
1
1
1
1
Gas Units  
Gas Units  
Gas Units  
State  
1st 3 bytes of gas units are written here as ASCII  
characters.  
0 = Enabled, 1 = Disabled  
1 = Gas Value updated with most recent message.  
0 = Gas Value not updated.  
In seconds since last update.  
8
1
1
1
1
Gas Value Valid  
Gas Value Age  
Sensor Data Age  
I/O State  
9
Initial (and max) value = 0xffff  
Age since last message, containing data from this  
sensor in seconds. Initial (and max) value = 0xffff  
255 = unknown, 0=Warm up, 1 = Ready, 2 = Trouble,  
3= Cal/Setup  
10  
11  
Alarm  
Status  
Audion On Status  
Alarm Latching  
Preference  
Latched  
12  
13  
14  
1
1
1
0=No, 1=Yes  
0=No, 1= Yes  
On Caution (0=No, 1= Yes)  
Alarm  
Preference  
Alarm  
Preference  
Audio  
Preference  
Audio  
Preference  
Audio  
Preference  
Audio  
Preference  
Audio  
Preference  
Spare  
Latching  
15  
16  
17  
18  
19  
20  
21  
1
1
1
1
1
1
1
On Warning(0=No, 1= Yes)  
On Alarm(0=No, 1= Yes)  
On Caution (0=No, 1= Yes)  
On Warning(0=No, 1= Yes)  
On Alarm(0=No, 1= Yes)  
On Trouble(0=No, 1= Yes)  
On Auxilary(0=No, 1= Yes)  
Latching  
On  
On  
On  
On  
On  
22-24  
1
2
3
4
5
6
7
25..49  
50.-74  
75.- 99  
100-124  
125..149  
150.-174  
175.-  
8
199  
The Driver expects similar a Data array format to send data to the Client when acting as a  
Server.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual  
Appendix A.3. Driver stats  
Page 17 of 19  
In addition to the standard FieldServer operating statistics the driver can expose certain key  
stats in a Data Array which can then be monitored by an upstream device. Adding the  
following to the configuration file will activate these stats for a driver configured as a Client.  
// Expose Driver Operating Stats.  
Data_Arrays  
Data_Array_Name,  
Infra-stats,  
Data_Format,  
UINT32,  
Data_Array_Length  
200  
Stat  
Stats  
#
Description  
0
1
2
3
INFRA_TROUBLE_MSG_RECV  
Number of trouble messages received  
Number of Alarm as well as Trouble  
messages reported  
Number of Alarm messages reported  
Number of Gas Value messages  
reported  
INFRA_TROUBLE_WITH_ALARM_MSG_RECV  
INFRA_ALARM_MSG_RECV  
INFRA_GAS_VALUE_MSG_RECV  
Number of Gas value as well as Alarm  
messages reported.  
4
INFRA_GAS_VALUE_WITH_ALARM_MSG_RECV  
5
6
INFRA_LOCK_MSG_RECV  
INFRA_BLANK_MSG_RECV  
Number of Lock messages reported  
Number of Blank messages reported  
Number of discarded messages  
starting with 0xB1 with length 49 bytes  
Number of discarded messages not  
starting with 0xB1 with length 49 bytes  
Number of discarded messages with  
length not 49 bytes.  
Length of the latest discarded  
message with length not 49 bytes.  
Number of messages discarded  
because of bad checksum.  
10  
11  
12  
13  
20  
INFRA_ST_0xB1_49_RECV_DISC  
INFRA_BAD_ST_49_RECV_DISC  
INFRA_NOT_49_RECV_DISC  
INFRA_NOT_49_RECV_BYTES_DISC  
INFRA_BAD_CRC_MSG_DISC  
For the node connected at R1; Offset = Stat number  
Example: The number of messages discarded because of bad start can be found at Offset 11  
in Infra-Stats Data Array.  
For the node connected at R2; Offset = 100 + Stat number  
Example: The number of messages discarded because of bad start can be found at Offset  
111 in Infra-Stats Data Array.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual  
Appendix B. Driver Error Messages  
Page 18 of 19  
Some configuration errors might produce an error every time a poll is generated. This will fill the  
error buffer quickly and not add any clarity. For this reason the driver suppresses subsequent  
similar messages. Thus it is possible for the same error produced by multiple Map Descriptors  
to produce only one error message. Subsequent error messages can be seen on the driver  
message screen.  
Note : In the actual message you will see that %d has been replaced by an integer, %s by text  
indicating a data array name or map descriptor name and %x by two hex characters.  
Error Message  
INFRA: #1 Err. Da <%s>  
length Reqd/exist <%d/%d>  
Md <%s> where md offset  
<%d>ψ  
Description and Action Required  
This error will be generated when the driver tries to store data for a  
sensor but the corresponding Data Array is not long enough. Set the  
Data Array length as indicated..  
Honeywell Zellweger IR-148-8.8-Channel or another unit is connected  
at the indicated port of the FieldServer but the Configuration file does  
not define a Map Descriptor to capture data from this unit. Change the  
CSV file to define a Map Descriptor to communicate with this device if  
required.  
INFRA:#2 Err. Incoming data  
is being abandoned on port R-  
P%d ψ  
INFRA:#3  
Node_id %d, Valid 1-8  
ERR.  
Invalid If there are multiple nodes then make the Node_ID the number of  
points (sensors) for which Zellweger units are configured.  
In Simulation mode the driver can send messages from files indicated  
by the Map Descriptor name. Check that the required file exists and  
that it is not in use by another application, or change the mode from  
simulation to operation by deleting the parameter  
“INFRA_SIMULATION” from .the CSV file.  
Infra:#4 Err. Test file <%s> not  
found.  
INFRA:#11 Err. Illegal MD  
Function for Md <%s>ψ  
INFRA:#12 Err. Illegal MD  
length <%s>ψ  
Set Map Descriptor’s function to Passive_Client if driver is configured  
as a Client or wrbc if configured as a Server.  
The Map Descriptor length parameter is either not defined or set to 0.  
Set the Map Descriptor length to 100.  
INFRA:#13  
Err.  
Illegal  
This error will be generated if you are using the Infra_func parameter  
with an incorrect value. See section 0 for legal values.  
This error will be generated when the driver tries to send a message to  
the Client, but the Data Array used to compose the message is  
insufficiently long to hold information for all 8 sensors. Set the Data  
Array length as indicated.  
Infra_func for Md <%s>ψ  
INFRA:#21 Err. Da <%s>  
length Reqd/exist <%d/%d>  
Md <%s> where md offset  
<%d>ψ  
In Server mode the driver does not send messages from lines starting  
with # or //. Change the Data_Array_Offset parameter for the indicated  
line in the ini file.  
INFRA:#22 Err. Diagnostic line  
<%d> ignored.ψ  
If an Upstream Device writes a value at a memory location under the  
influence of the given Map Descriptor, the Write-thru operation will be  
cancelled as the Driver cannot write to an UnfraTox unit..  
INFRA:#41 FYI. Write-thru not  
Possible On MD <%s>  
Infra:#51 FYI. You could use  
an Array called <%s> to  
expose diagnostic info.  
It is possible to define a Data Array known as “Infra-stats” (see 0) This  
Data Array is very useful for statistics purposes.  
ψ Edit CSV file, download the modified file and reset the FieldServer to have the changes take effect.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
FS-8700-102 Honeywell Zellweger IR-148-8_8-Channel Manual  
Page 19 of 19  
THIS PAGE INTENTIONALLY LEFT BLANK  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  

Motorola MOTOSLVRTM L9 User Manual
Maxtor Personal Storage 3000XTX01FWRA160 User Manual
LG Electronics TM250 User Manual
HTC WIZA100 User Manual
Hitachi Travelstar HTS545032B9A300 User Manual
Hamilton Beach Coffeemaker TE419 User Manual
Echo Bear Cat 73413 User Manual
Casio DQR 100U User Manual
Briel DOMUS ES161A TB User Manual
Apple IPOD HI FI User Manual